Permit: T03CM04586

Parcel: 124081690


Addresses:

1321 E 10TH ST


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T03CM04586

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2004 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
06/04/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/ 1) OK TO BACKFILL-LEAVE ACCESS TO TOP OF EJECTOR 2) INSTALL BACKFLOW VALVE ON EJECTOR
05/27/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/ 1) OK TO FILL DITCH 2) NEED 2 WAY CLEANOUT FOR GUEST HOUSE 3) BACKFLOW VALVE IN EJECTOR UNIT
04/29/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*/ 1) YOU NEED A 2 WAY 3" BLDG CLEANOUT 2) YOU NEED A BACK CHECK VALVE ON DISCHARGE LINE 3) YOU NEED ANOTHER 2" CLEANOUT, YOU ARE OVER 135 DEGREE ON HORIZNOTAL DRAIN LINE 4) NOT IN THE CODE FOR SAME OWNER HOUSE AND GUEST HOUSE, BUT I WOULD ADVISE YOU TO INSTALL A BACK WATER VALVE ON EXITING HOUSE SEWER, IF THERE IS A STOPPAGE DOWN STREMA FROM 2" TO 3" CONNECTION, WHEN EJECTOR IS FULL AND STARTS PUMPING, THE ONLY PLACE IT CAN GO IN YOUR MAIN HOUSE, PUMP INTO LOWEST FIXTURE LIKE A TUB OR SHOWER