Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM04571
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*/ 1) ADDITIONAL FLOOR SINK SUBJECT TO APPROVED PLAN. 2) CORRECTIONS MADE OK. 3) OK TO BACKFILL. | |
11/04/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*/ 1) YOU MUST CORRECT THE ADDRESS ON THE PERMIT BEFORE THE NEXT INSPECTION 2) PLEASE REMOVE DEBRIS FROM TRENCH WHERE IT IS COVERING CONNECTIONS 3) REQUIRED 2 PIPE DIAMETERS BETWEEN WEIR OF TRAP AND POINT OF VENT AT FLOOR SINK INSTALLED AT SERVICE SINK AREA NOT ON PLAN. REVISE PLAN OR INSTALL PER APPROVED PLAN | |
11/03/2003 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*/ DOORS LOCKED - NO ACCESS. |