Permit: T03CM04567

Parcel: 10711279A


Addresses:

3022 N GERONIMO AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/20/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
FINAL WARNING! GET YOUR SCREEN DONE RIGHT OR PAY A REINSPECTION FEE FOR EVERY UNIT.
06/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/15/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ALL EXPOSED WIRING MUST BE PROTECTED FROM PHYSICAL DAMAGE (RODANTS, ETC...)
2) REMOVE ALL SCREENS FROM DRYER VENTS. PROVIDE SCREENS IN EXHAUST T-TOPS
3) PROVIDE HEAT STRIP UNIT #1
05/23/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE FLAT CONDENSATE TRAPS
2. MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY.
3. RELOCATE FAN COILS 1, 3, 5 BE SURE ALL UNITS HAVE PROPER FUSES.
4. UNIT #7 OK
5. PROVIDE T-STAT & WIRE FOR UNIT 1
6. PROVIDE BUSHING ON SUCTION LINE AS NEEDED AT FAN COIL CONNECTION.
7. BE SURE ALL T-TOPS HAVE SCREENS EXCEPT DRYER VENTS
8. STAT WIRE ON ROOF MUST BE PROTECTED.