Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM04566
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) OK TO CLEAR |
|
| 07/29/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) FINISH MAKE UP OF MAIN DISCONNECT 2) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE EQUIPMENT 3) INSTALL GROUNDING ELECTRODE 4) PLEASE PROVIDE A LETTER FOR TORQUE OF EQUIPMENT |
|
| 12/10/2004 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 12/09/2004 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :*/S/B 02010 UG PVC FROM BLDG TO TEP TX FMR-=PARTIAL |