Permit: T03CM04564

Parcel: 10819224A


Addresses:

811 E WETMORE RD 04


Inspection Status: Approved

Inspection History: ENGINEERING - FINAL

Permit Number - T03CM04564

Inspection Description - ENGINEERING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2006 ENGINEERING - FINAL Approved PER INSP CARD
07/19/2006 ENGINEERING - FINAL Correction Required PROVIDE AN APPROVED REVISED (PLAN,DRAWING,STATEMENT) CERTIFIED (STAMPED) BY A PROFESSIONAL ENGINEER SHOWING CHANGES MADE TO THE SITE DRAINAGE AND SPECIFIC ITEMS IDENTIFIED ON THE 7/14/06 FINAL GRADING INSPECTION FOR PERMIT#T03BU01928:

1) CALCULATED FLOW VOLUME (Q) OF COURTYARD (CHANNEL)
2) ELEVATIONS OF CHANNEL TO SHOW DRAINAGE
3) SUMP PUMP SIZE AND SPECS FOR REVIEW
4) ELEVATION READINGS OF WATER HARVESTING AREA ON WEST SIDE OF COURTYARD.
07/17/2006 ENGINEERING - FINAL Cancelled IVRS - AP canceled
07/14/2006 ENGINEERING - FINAL Denied SEE NOTES FROM FINAL GRADING INSPECTION FOR PERMIT #T03BU01928
07/13/2006 ENGINEERING - FINAL Cancelled IVRS - AP canceled
07/06/2006 ENGINEERING - FINAL Denied DENIED, SITE WORK NOT COMPLETED, STILL UNDER CONSTRUCTION.
PROVIDE A REVISED GRADING PLAN, CERTIFIED BY AN ENGINEER, SHOWING CHANGES AND/OR PROPOSED CHANGES MADE TO THE SITE.
07/03/2006 ENGINEERING - FINAL Cancelled IVRS - AP canceled
10/28/2005 ENGINEERING - FINAL Partial Approval TEMP C OF O: C OF O NOT TO BE GIVEN UNTIL ALL SITE WORK IS COMPLETED AND FIANL GRADING INSPECTIONFOR PERMIT#T03BU01928 IS COMPLETED AND APPROVED
08/25/2005 ENGINEERING - FINAL Denied DENIED, UNABLE TO PROVIDE A SAFE ENVIRONMENT FOR OCCUPANTS OF BLDG. DUE TO CONSTRUCTION ACTIVITY, (HEAVY EQUIPMENT TRAFFIC, OVERHEAD WORK, GRADE
CHANGES, INCOMPLETE AND OBSTRUCTED PEDESTRIAN
PATHWAYS).

NOTE: DURING THE INSPECTION IT WAS APPARENT THAT THE BUILDING IS ALREADY OCCUPIED BY THE PUBLIC.


DRAINAGES STRUCTURES NOT INSTALLED PER APPROVED PLAN.
08/24/2005 ENGINEERING - FINAL Approved OK FOR TEMP C OF O PER J FEMLING