| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. CLOSET FLANGES OK 2. NOTE: THE FIRST FIVE INCHES A.F.F IS DEDICATED TO THE CABINET TOE SPACE. A CLEANOUT IN THIS AREA IS USELESS. |
|
| 05/01/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. REC'D LETTER FROM ENGINEER CONCERNING SHEAR WALL DAMAGE -- WILL ENTER INTO FILE. OK TO COVER WALLS. NEED TO SEE CLOSET FLANGES. |
|
| 04/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* YOU NEED TO RFI ENGINEER AT TLCP FOR FIX ON DAMAGED SHEAR WALL AT GRID 3.2 DO NOT COVER!! |
|
| 04/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PVC DWV OK WITH EXCEPTIONS PVC MAY NOT BE DIRECTLY EMBEDDED IN CONCRETE OR MASONRY. 2. NEED TO SEE CLOSET FLANGE. 3. OK TO INSULATE HOT. |
|
| 04/07/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/27/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PVC DWV FOR 2ND, 3RD AND 4TH FLOOR OK WATER TEST OK 2) CPVC AND PEX WATER OK 3) TUBS OK 4) OK TO COVER ALL AREAS 2ND, 3RD AND 4TH 5) ROOF DRAINS OK TO COVER |