Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM04561
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK TO COVER ALL AREAS | |
| 03/30/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TRAP ARMS WHICH EXCEED 1/4" PITCH PER FOOT RISK HAVING THE POINT OF VENT BELOW THE TRAP WEIR, WHICH PROMOTES SIPHONAGE-CHECK ALL TRAP ARMS AND CORRECT THE PITCH AS REQUIRED | |
| 03/29/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) THIRD FLOOR-STILL SUPPORTING FITTINGS-NOT PIPE. PIPE SUPPORTS TO BE ADJACENT TO FITTINGS, NOT ON THEM. 2) WATER PIPING MAY NOT PASS OVER ELECTRIC SERVICE PANEL. 3) 2ND FLOOR-POINT OF VENT MAY NOT BE BELOW THE??OF THE TRAP | |
| 03/28/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT PIPE, NOT FITTINGS. 2) SECURE ALL CLOSET FLANGES WITH APPROVED SCREWS. TRAP ARMS TO BE INSTALLED WITH 1/4" PITCH PER FOOT. | |
| 03/25/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |