Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04561
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/11/2006 | ELECTRIC - FINAL | Partial Approval | 1) CHANGED TO PARTIAL DUE TO NON COMPLETION OF ELECTRICAL FINAL 2) GROUNDING ELECTRODE CONDUCTOR HAS BEEN REPAIRED THIS IS ALL I INSPECTED |
|
| 08/19/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) POST BOND FOR TEMP C OF O |
|
| 08/16/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR FUEL AND TESTING POWER: 1101-1110, 1201-1210 AND 811 E. WETMORE #1 (HOUSE PANEL) |
|
| 08/15/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FEEDERS ARE NOT ALL TERMINATED 2) BUSHINGS MISSING AT EMT CONNECTORS 3) LABEL METER BASES |