Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/02/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PLAN SHOWS A FUSED 100 AMP DISCONNECT BY PAINT BOOTH. 2) PANEL 'B' FEEDS PAINT BOOTH - PLAN SHOWS IT SHOULD BE MARKED 'A'. 3) BLUE WIRE IN PANEL USED FOR NUETRAL MUST BE WHITE OR TAPED WHITE ALL THE WAY AT PANEL AND PAINT BOOTH. 4) MULTIPLE WIRES ON GROUND TERMINATION IN SPRAY BOOTH CABINET. 5) FINISH MOTOR TERMINATION IN BOOTH CABINET. 6) REMOVE ALL UNUSED CUT TERMINATIONS IN CABINET. 7) WIRES TOPPED IN GUTTER BELOW PANEL 'A' S/BE 150 A SIZE. 8) PERMANENTLY LABEL A AND CIRCUIT BREAKERS. |