Permit: T03CM04538

Parcel: 141175990

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM04538

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2004 FRAMING Approved IVRS - Inspection 0000*
01/20/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*
01/16/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) OK TO INSULATE 2) FIX TRUSS 3) SECURE SWITCH BOX AT PEN
01/13/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) MORE NAILS LEDGER TO STUD 2) BLOCK ALL MECHANICAL DUCTS 3) NAIL OSB GARAGE TO HOUSE WALL AT BANG PLATE 4) NEED POTABLE WATER TEST 5) BROKEN STUD DINNING ROOM REAR WALL 6) GABLE END 45 DEGREE BRACES, BLOCK AT TRUSS CHORDS NAIL BRACES TO BLOCKS PER DETAIL, NOT TOE NAILED 7) STUD AT REAR SHOWER NEEDS FHA STRAPS, HOLE TO BIG 8) SAME BATHROOOM STUD AT LAV. CUT TO DEEP, BOTTOM PLATE IS SPLIT 9) NEED BACKING AT TUB SIDES 10) INSULATE LARGE MECHANICAL METAL BOX IN CEILING 11) GAP WEEP SCREEP FRONT BEDROOM 12) LARGE TRUSS BRACES FRONT TO GO FROM BOTTOM TO RIDGE 13) GAS/DWV-OK