Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM04538
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2004 | FRAMING | Approved | IVRS - Inspection 0000* | |
01/20/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
01/16/2004 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO INSULATE 2) FIX TRUSS 3) SECURE SWITCH BOX AT PEN | |
01/13/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) MORE NAILS LEDGER TO STUD 2) BLOCK ALL MECHANICAL DUCTS 3) NAIL OSB GARAGE TO HOUSE WALL AT BANG PLATE 4) NEED POTABLE WATER TEST 5) BROKEN STUD DINNING ROOM REAR WALL 6) GABLE END 45 DEGREE BRACES, BLOCK AT TRUSS CHORDS NAIL BRACES TO BLOCKS PER DETAIL, NOT TOE NAILED 7) STUD AT REAR SHOWER NEEDS FHA STRAPS, HOLE TO BIG 8) SAME BATHROOOM STUD AT LAV. CUT TO DEEP, BOTTOM PLATE IS SPLIT 9) NEED BACKING AT TUB SIDES 10) INSULATE LARGE MECHANICAL METAL BOX IN CEILING 11) GAP WEEP SCREEP FRONT BEDROOM 12) LARGE TRUSS BRACES FRONT TO GO FROM BOTTOM TO RIDGE 13) GAS/DWV-OK |