Permit: T03CM04535

Parcel: 14027051D

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T03CM04535

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
03/04/2004 PLUMBING - GAS PRESS TEST FNL Approved
02/12/2004 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*/ 1) MUST REMOVE UNIONS IN LINE EXCEPT AFTER SHUT OFF VALVES FOR REGULATORS OR CONNECTIONS TO EQUIPMENT SEE SEC. 1211.10 - 94 UPC. 2) MUST PROVIDE TEST GUAGE REQUIRED FOR MED. PRESSURE, SEE SEC. 712.4.2 - 94 UPC. - 60 LBS MIN. 3) ALL REGULATORS MUST BE PERMANENTLY TAGGED SAYING [WARNING ½ TO 5 LBS NATURAL GAS PRESSURE. DO NOT REMOVE] SEE SEC. 1218.4 EXCEPTION #4