Permit: T03CM04534

Parcel: 11615087J

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/19/2005 MECHANICAL - INTERMEDIATE Approved
07/14/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/11/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OXYGEN LINE NOT HOLDING PRESSURE
07/07/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEW STEM LINES-CU. 52 PSI
2) REMOVE PLENIUMN NON RATED GLASS INSULATION FROM ABOVE GRID
3) OK TO COVER HARD DUCT AND PIPE, RETURN, SUPPLY AND EXHAUST DUCT
06/23/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* RM 1606 PSI VACUM 80, OXYGEN 100, MED AIR 100 . MED GAS MODIFICATION PROGRESSING
06/21/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/16/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/18/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* 2'' STEAM LINE TO 2 IN AIR HANDLERS AND TWO ( 2) DUCT MOUNTED 100 PSI
01/24/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* SUSPENDED SUPPLY DUCT DOWN TO TERMINALS PROGRESSING. CHECKED FIRE DAMPER/ COM? PROGRESSING
12/17/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/SUPPLY/RETURN HEATING WATER TO VAV'S 100 PSI OK. EXISTING MECH. PIT, FUTURE BASEMENT PARTIAL
11/10/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/SUSPENDED ROUGH DUCT - SUPPLY RETURN
07/08/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) EAST BLDG ADDN. CHILLED WATER/HOT WATER 2) PIPING UNDERGROUND SUPPLY/RETURN LPS 3) 150 PSI UNDER NORTH PARKING LOT FROM MECH PLANT TO EAST BLDG ADDITION
06/14/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) ? GRD. CHILLED/HOT WATER LINES CONTINUES AROUND NORTH END OF PKG. LOT
05/20/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/17/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) CW 10" - CHILLED WTR LINES SUPPLY/RETURN - HOT WTR 6" STEEL PIPE - UNDER PRKG LOT UNDERGROUND. 2) DETAIL FROM ENGINEER FOR INSUL. AS NECESSARY PRIOR TO BACKFILLING.