Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM04534
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2005 | MECHANICAL - INTERMEDIATE | Approved | ||
07/14/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/11/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OXYGEN LINE NOT HOLDING PRESSURE |
|
07/07/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEW STEM LINES-CU. 52 PSI 2) REMOVE PLENIUMN NON RATED GLASS INSULATION FROM ABOVE GRID 3) OK TO COVER HARD DUCT AND PIPE, RETURN, SUPPLY AND EXHAUST DUCT |
|
06/23/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM 1606 PSI VACUM 80, OXYGEN 100, MED AIR 100 . MED GAS MODIFICATION PROGRESSING | |
06/21/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/16/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/18/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2'' STEAM LINE TO 2 IN AIR HANDLERS AND TWO ( 2) DUCT MOUNTED 100 PSI | |
01/24/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED SUPPLY DUCT DOWN TO TERMINALS PROGRESSING. CHECKED FIRE DAMPER/ COM? PROGRESSING | |
12/17/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/SUPPLY/RETURN HEATING WATER TO VAV'S 100 PSI OK. EXISTING MECH. PIT, FUTURE BASEMENT PARTIAL | |
11/10/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/SUSPENDED ROUGH DUCT - SUPPLY RETURN | |
07/08/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) EAST BLDG ADDN. CHILLED WATER/HOT WATER 2) PIPING UNDERGROUND SUPPLY/RETURN LPS 3) 150 PSI UNDER NORTH PARKING LOT FROM MECH PLANT TO EAST BLDG ADDITION | |
06/14/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) ? GRD. CHILLED/HOT WATER LINES CONTINUES AROUND NORTH END OF PKG. LOT | |
05/20/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/17/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) CW 10" - CHILLED WTR LINES SUPPLY/RETURN - HOT WTR 6" STEEL PIPE - UNDER PRKG LOT UNDERGROUND. 2) DETAIL FROM ENGINEER FOR INSUL. AS NECESSARY PRIOR TO BACKFILLING. |