Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM04534
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/17/2005 | PLUMBING - INTERMEDIATE | Partial Approval | PHASE 2 REMODEL PROVIDE CORRECT PERM CAP FOR 4" & 6' RAW DRAIN? IN RADIOLOGY 1238 & 1240. REROUTE OF 4" WASTE OK. EXISTING WASTE RE ROUTE IN 1252 A DOES NOT EXIST. NEED TO RE OPEN 3035, 3036 FOR PHASE II. | |
04/11/2005 | PLUMBING - INTERMEDIATE | Partial Approval | ||
03/04/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RMS # 1225, 1226, 1227 OK TO COVER ALSO 1232. N/H OK. COPPER OK. OK TO INSULATE. | |
02/24/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT FOR SOIL 1137, TREATMENT 1132, 1133, 1134, 1136, AND 4" VENT FROM 1ST FLOOR LEVEL THRU ROOF FOR BASEMENT EJECTOR PUMP OK. H20 PIPING IN SAME ROOMS OK | |
02/23/2005 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
02/01/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* APPROVED 1) VENT SYSTEM FOR CORRIDOR $ 1224, #1135 IS UNDERSIZED SEE TABLE 7-5 NOTE 2) N/H DWV IN ALL OTHER AREAS OK TO COVER COPPER OK TO COVER ALL ROOF DRAINS OK TO COVER. | |
01/31/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1 N/H DWV ALONG CORRIDORS # 1162, 1170, 1173, 1157, 1201 AND VENTS SYSTEMS OK AS NOTED ON PLAN. 2) ROOF DRAINS AS NOTED ON PLAN OK TO COVER. 3) COPPER IN THESE AREAS OK 4) TOILET ROOMS 1106, 1107 AND JANITORS 1111 OK TO COVER. | |
12/16/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)PLUMBER REDLINING PLAN AS INSTALLATION CONFLICTS WITH PLAN 2)OVERHEAD DOMESTIC WATER MAINS AND BRANCHES TO ISOLATION VALVES OK TO INSALATE. | |
12/08/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/PROVIDE RED LINE DRAWING ON SITE AT TIME OF INSPECTION OR INSTALL PER APPROVED PLAN | |
11/01/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)OK TO POUR CONCRETE | |
10/27/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/UNDERGROUND FOR #1107, #1108 & #1111 OK TO COVER. 3" COPPER WATER SERVICE STUB UNDER SLAB OK TO COVER | |
05/04/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |