Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) PETITION OF APPEAL # 05-05-08 TURNED IN |
|
| 03/23/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL APPROVAL OK FOR TEMP C OF O. RECEIVED ( 3) COPIES OF BACKFLOW CERTIFICATIONS. | |
| 03/23/2005 | PLUMBING - FINAL | Partial Approval | OK TEMP C OF O | |
| 03/21/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CLEANOUT IN MENS RESTROOM FLOOR NEEDS TO BE FLUSH TO PREVENT TRIPPING HAZARD. SECURE MOP SINK FAUCET BRACKET IN DOW STAIRS MOP SINK AREA AND CAULK THIS FIXTURE TO BE WATER TIGHT. ANSUL VALVE REQUIRES SIGNAGE FOR LOCATION. CONDENSATE MAY NOT GO TO SINKS, PLEASE PROVIDE PETITION OF APPEAL. TOPPLER BUILDING HOT WATER SYSTEM HAS NOT PRESSURE. PROVIDE BACKFLOW CERTIFICATION COPIES TO BE TURNED IN (3). EXPOSE PIPING FOR SEWAGE EJECTOR PUMPS. | |
| 03/09/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY RECEIVED LETTER FROM ADDITION OF HOSE BIB AND GREASE INTERCEPTOR LISTING FROM HAYPEN | |
| 02/25/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY. 1) CALL IN ALL INSPECTIONS THAT HAVE NOT BEEN APPROVED. 2) 3050 & 3052 1) INSTALL VALVE & PLUG AT DRYER LOCATION. 2.1) COMPLETE HOOK UP FOR GAS AT STOVE. 2.2) VENT FROM WATER HEATER TO BE 2' ABOVE ANY BUILDING WHEN WITHIN 10' |