Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03CM04493
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2004 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
02/19/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NO FUSES IN DISCONNECT 2) #6 CU REQUIRED ALL THE WAY TO THE UNIT INCLUDING THE WHIP CIRCUIT AMPS 51.4/57.6, #8 CU IS GOOD FOR 55 AMPS, BUT OVER CURRENT PROTECTION IS 60/60. I DON'T THINK YOU CAN GET A 55 AMP BREAKER FOR THAT SERVICE PANEL, YOU CAN FUSE DOWN AT DISCONNECT | |
02/12/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
02/09/2004 | BUILDING - FINAL | Partial Approval | 1) FROM LAST INSPECTION, MARK HEAT STRAP AND SIZE FOR FUSES | |
02/03/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SEE LAST INSPECTION | |
01/16/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) TOO MANY UNFINISHED ITEMS. A/C DISCONNECT NEEDS WORKING CLEARANCE. LABEL TO BE MARKED ON FURNACE FOR AMPERAGE 2) ELECTRIC TRIM NOT DONE 3) FLU CAP MISSING 4) WHERE DOES CONDENSATE DUMP IT'S WATER 5) WINDOW IN OFFICE TO BE SAFETY GLASS |