Permit: T03CM04493

Parcel: 141175270

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM04493

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/19/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NO FUSES IN DISCONNECT 2) #6 CU REQUIRED ALL THE WAY TO THE UNIT INCLUDING THE WHIP CIRCUIT AMPS 51.4/57.6, #8 CU IS GOOD FOR 55 AMPS, BUT OVER CURRENT PROTECTION IS 60/60. I DON'T THINK YOU CAN GET A 55 AMP BREAKER FOR THAT SERVICE PANEL, YOU CAN FUSE DOWN AT DISCONNECT
02/12/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*
02/09/2004 BUILDING - FINAL Partial Approval 1) FROM LAST INSPECTION, MARK HEAT STRAP AND SIZE FOR FUSES
02/03/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) SEE LAST INSPECTION
01/16/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) TOO MANY UNFINISHED ITEMS. A/C DISCONNECT NEEDS WORKING CLEARANCE. LABEL TO BE MARKED ON FURNACE FOR AMPERAGE 2) ELECTRIC TRIM NOT DONE 3) FLU CAP MISSING 4) WHERE DOES CONDENSATE DUMP IT'S WATER 5) WINDOW IN OFFICE TO BE SAFETY GLASS