Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/20/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 01/09/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) A TRAP ARM MAY ONLY CHAGE DIRECTION 90 DEGREE WITHOUT THE USE OF A CLEANOUT 2) 1 1/2" TRP ARM MAY NOT EXCEED 3'-6" FROM WEIR OF TRAP TO POINT OF VENT 3) CONTRACTOR TO INSURE CORRECTIONS MADE. WILL VERIFY ON FINAL |
| 11/20/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) AREA DRAINS TO DAYLIGHT ON SOUTH SIDE OK TO COVER. 2) YARDWATER PIPING FROM METER THRU RPPBP INTO BLDG OK. OK TO COVER. |
| 11/19/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE REDLINE 'AS BUILTS' TO REFLECT INSTALLATION CHANGES FROM THE PLAN. 2) ABS UNDERGROUND OK. TIE-IN TO EXISTING OK. OK TO COVER. 3) YOU MIGHT WANT TO REVIEW 511.2 94 UPC - LOCATION OF METER. |