Permit: T03CM04485

Parcel: 115151910


Addresses:

635 W LESTER ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/20/2004 PLUMBING - INTERMEDIATE Approved
01/09/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) A TRAP ARM MAY ONLY CHAGE DIRECTION 90 DEGREE WITHOUT THE USE OF A CLEANOUT 2) 1 1/2" TRP ARM MAY NOT EXCEED 3'-6" FROM WEIR OF TRAP TO POINT OF VENT 3) CONTRACTOR TO INSURE CORRECTIONS MADE. WILL VERIFY ON FINAL
11/20/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) AREA DRAINS TO DAYLIGHT ON SOUTH SIDE OK TO COVER. 2) YARDWATER PIPING FROM METER THRU RPPBP INTO BLDG OK. OK TO COVER.