Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/24/2004 |
FRAMING |
|
Approved |
|
| 02/23/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) CANCELLED ON SITE BY MARTI 2) PROVIDE PROOF OF FRAME APPROVED INSPECTION |
| 12/08/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BANG PLATES MISSING THRU-OUT 2) UFER NOT CONNECTED TO PANEL (SHORT) 3) CHECK ALL UFER BOLTS 12" MAXIMUM FROM PLATE EDGE 4) FIRE BLOCK AT CHASE TRIANGE UPSTAIRS |
| 12/02/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) UFER GROUND NOT GROUNDED TO PANEL 2) NAIL PROTECT ELECTRIC WITHIN 1 1/4" FROM EDGE OF STUD 3) STAIR TREAD MISSING 4) INSULATE BEHIND TUBS 5) SECURE GAS LINE AT FURNACE 6) MOVE ELECTRICAL WIRES AWAY FROM GUSSETT PLATES 7) BLOCK REGISTER AT MASTER BATH 8) COMPLY WITH TABLE E3702.1, 2000 IRC, FLAT WIRES NOT ALLOWED TO BE STAPLED ON IT'S SIDE 9) PERMITS CALL FOR ISLAND OVERHANG, OUTLET NOT ALLOWED IF COUNTER OVER HANGS MORE THAN 6" |