Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM04450
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/15/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) PLUMBING CORRECTIONS MADE OK. RPZ CERTS ON FILE WITH TUCSON WATER. 2) PLUMBING FINAL OK. 3) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. | |
01/14/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ OK FOR TEMP POWER. CONTRACTOR PRODUCED TEMP POWER FOR TESTING - AND SUBSTITUTED GAS INSTEAD. DON'T WE HAVE THE PROPER FORM? OK FOR GAS SUBJECT TO MECH. INSPECTOR AND STEVE LONG | |
01/12/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) I DEVICE PER I BACKFLOW DEVICE. 2) DRAINAGE FITTINGS TO BE USED ON ALL DRAINS. 3) CLEAN OUTS AT 135o CHANGE OF DIRECTION ON DRAINS. 4) P-TRAP ON INDIRECT DRAIN OVER 5' IN LENGTH. 5) SECURE T&P DRAIN LINES. 6) ALL GAS APPLIANCES TO BE INSTALLED OR CAP GAS PIPING. 7) WTR SEAL ALL FIXTURES. 8) ALL DRAINS TO BE SECURED AND HAVE 1" MIN. AIR GAP AT FLOOR SINKS. |