Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ OK TO COVER BAR AREA. |
| 11/18/2003 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) COPPER AT BAR AREA LOOSE IN WALL 2) FHA STRAP IS NON-FUNCTIONAL-NEED TO TIE BOTTOM MEMBER INTO ITSELF |
| 10/24/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/1) GAS PRESSURE TEST OK. 2) ABS IN KITCHEN AREA OK. COPPER IN KITCHEN AREA OK. 3) OK TO COVER WALLS IN KITCHEN AREA. |
| 10/06/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1) PLEASE POST THE CORRECT SUITE NUMBER. 2) SEE NOTE #1 FROM 10/01/03. PLEASE HAVE ROUGH SOIL ADDED TO YOUR PERMIT BEFORE NEXT INSPECTION. 3) HAVE PLUMBER READ PLUMBING SPEC. NOTE #18 AND COMPLY. DO NOT COVER. |
| 10/01/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/1) HAVE 03005 - PLUMBING ROUGH SOIL - ADDED TO PERMIT AND CALL UNDERGROUND INSPECTION ON THIS CODE. 2) ABS DWV UNDERGROUND OK. WATER TEST ONE RISER TO TEN FEET OK. P.O.C. TIE-INS OK. 3) OK TO BACKFILL. 4) NEED TO SEE TYPE K COPPER LOOPED FROM BAR TO EXISTING FLOOR SINK BEFORE YOU POUR. ALSO NEED TO SEE FLOOR SINKS AND DRAINS INSTALLED. |