Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM04450
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ OK TO COVER BAR AREA. | |
11/18/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) COPPER AT BAR AREA LOOSE IN WALL 2) FHA STRAP IS NON-FUNCTIONAL-NEED TO TIE BOTTOM MEMBER INTO ITSELF | |
10/24/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/1) GAS PRESSURE TEST OK. 2) ABS IN KITCHEN AREA OK. COPPER IN KITCHEN AREA OK. 3) OK TO COVER WALLS IN KITCHEN AREA. | |
10/06/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/1) PLEASE POST THE CORRECT SUITE NUMBER. 2) SEE NOTE #1 FROM 10/01/03. PLEASE HAVE ROUGH SOIL ADDED TO YOUR PERMIT BEFORE NEXT INSPECTION. 3) HAVE PLUMBER READ PLUMBING SPEC. NOTE #18 AND COMPLY. DO NOT COVER. | |
10/01/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/1) HAVE 03005 - PLUMBING ROUGH SOIL - ADDED TO PERMIT AND CALL UNDERGROUND INSPECTION ON THIS CODE. 2) ABS DWV UNDERGROUND OK. WATER TEST ONE RISER TO TEN FEET OK. P.O.C. TIE-INS OK. 3) OK TO BACKFILL. 4) NEED TO SEE TYPE K COPPER LOOPED FROM BAR TO EXISTING FLOOR SINK BEFORE YOU POUR. ALSO NEED TO SEE FLOOR SINKS AND DRAINS INSTALLED. |