Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04440
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/11/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ OK TO OCCUPY. THE EM/EXIT LIGHTS OVER MAIN ENTRANCE/EXITS ARE NOT OPERABLE. THESE MUST BE REPAIRED OR REPLACED ASAP. ONLY ITEM PENDING. | |
05/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) ADDRESSES ON METER BASE. 2) CONNECTORS AT SIGN. 3) PERMAMENT PANEL I.D. AND INDEXES. 4) WALK-IN BOXES LIGHTING AND J-BOX COVERS. 5) TIME SWITCHES NEED PERM I.D. TAGS. 6) ROOF MTD DISCONNECTS, FAN SWITCHES, AND GFI NEED PERM I.D. TAG WITH PANEL AND CIRCUITS SERVING LINE SIDE. DO NOT MARK WITH I.D. NAME OF UNIT SERVED. |