Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ OK ROUGH BARRIER. |
| 03/11/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) CLAMPS NEEDED FOR MULTGANG BOXES. 2) SHEATH TO BE ΒΌ" INTO BOXES. 3) APPROVED CONNECTORS ARE NEEDED FOR METAL BOXES 373-5 (c). 4) TIGHTEN LOOSE FITTINGS AT PANELS. |