Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/09/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/06/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) OVER BOARD DOUBLE TOP PLATE AT ELECTRIC SERVICE INSTALL FHA STRAPS 2) SHEAR WALL 3 GARAGE NOT CLIPPED PER 10/DT-1 3) REVISE GAS PLAN TO ADD GAS TO PLATE 4) NO DWV WATER TEST 5) ACCESS TO ATTIC FURNACE OBSTRUCTED BY TRUSSES 6) HEADERS MUST BEAR ON TRIMMERS 7) PROVIDE PROOF THAT OFF SET FLOOR FLANGE IS UPC LISTED 8) NO TRUSS DRAWINGS ON SITE |