Permit: T03CM04395

Parcel: 13312006M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM04395

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2003 ELECTRIC - FINAL Approved CLEARANCE SUBJECT TO LAST INSPECTOR
11/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) FUSES IN MAIN SW FOR A & B MISSING - ALSO REJECT PINS. 2) FUSES IN AC UNITS MISSING. 3) EXIT LIGHTS NOT IN. 4) J-BOX IN CEILING ABOVE PANELS NOT MADE UP OR COVERED. 5) BATH ROOM FIXTURES MISSING, REAR DOOR ABOVE CEILING FIXTURE MISSING. 6) REAR ROOM 'A' FIXTURE MISSING J-BOX NEEDS X-RING. 7) ROOF OK - MECH. INSP TO OK FUSING.