Permit: T03CM04390

Parcel: 133261360


Addresses:

650 N KENT DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/23/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 15 PSI TEST IS OK. ALL CORRECTIONS HAVE BEEN MADE. OK TO ENERGIZE GAS.
09/18/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/1) ALL EXPOSED PVC DRAIN PIPE ON THE ROOF MUST BE PAINTED WITH LATEX PAINT TO PROTECT FROM SUN DAMAGE. 2)A/C UNIT IS OVERFUSED AT 50 AMP. 40 AMP IS MAX. FUSE SIZE. SEE UNIT DATA PLATE. 3) PROVIDE A MIN. 10 LB TEST ON NEW GAS PIPE. YOU CAN PUT A SHUT OFF VALVE AT THE POINT OF CONNECTION AND TEST FROM THERE TO THE UNIT ON THE ROOF. IF A UNION IS NECESSARY USE A REVERSE THREAD COUPLING AND NIPPLE.