Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/03/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRESTOP ABOVE HEADERS AT NAILER SOUTH EXTERIOR WALL 2) FIRESTOP OVERKNOTCH AT TOP PLATE FROM MAIN WATER LINE 3) FIRESTOP OVERKNOTCH AT TOP PLATE A/C LINES 4) FIREBLOCK AT BATHROOM EAST SOFFIT 5) ELECTRIC PLAN DOES NOT REFLECT CIRCUIT TO EXTERIOR 6) WASTE VENTS MUST BE FILLED TO ROOF TOPS WITH WATER/COPPER OK 7) GROUT TUB SHOE 8) IF YOU WISH TO OMIT PORCHES, YOU MUST TAKE PLANS TO PLAN REVIEW AND STAMP THE REVISIONS |
|
| 02/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST HAVE EXTERIOR GAS PIPING EXCAVATED FOR INSPECTION 2) 220/ELECTRIC NOT RUN TO RANGE 3) BLOCK 3 SIDES MECHANICAL DUCTS 4) INSTALL PLATE BOLTS WITHIN 12" EACH END BOTTOM PLATES 5) WHAT IS YELLOW ELECTRIC LOOPED IN UTILITY ROOM FOR ? 6) NO TEST DWV 7) PORCH NOT FRAMED 8) STOPPED INSPECTION |
|
| 01/03/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/MUST INSTALL PAPER, FOAM & WIRE LATHE PRIOR TO INTER. INSPECTION |