Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 01/02/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 12/30/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) PLAN CALLS FOR 1'-10" WIDE FTGS. 2) REMOVE DIRT FOR AROUND ABS PIPING IN FOOTING AND THEN WRAP ALL PIPING TO BE IN CONTACT WITH CONCRETE 3) MAINTAIN MINIMUM 3" REBAR TO DIRT 4) MASONRY COLUMN FTGS. NOT PER APPROVED PLAN 5) PLAN CALLS FOR FTG AND STEM; YOU ARE USING MONO-POUR (HAVE PLAN CHANGED) 6) PLAN CALLS FOR 3 REBAR IN FTG AND 2 TOP OF TEM 7) STOPPED INSPECTION |
| 12/23/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999* |