Permit: T03CM04365

Parcel: 128100530

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM04365

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ PROVIDE SECONDRY DRAIN PANS (WHICH WERE REMOVED) UNDER AIR HANDLERS AND DRAIN IN A CONSPICUOUS LOCATION OR USE OVERFLOW SENSORS. LEAVE OUT TILES IN THESE AREAS FOR INSPECTION. WILL CHECK ON FINAL.
11/13/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ NOTE: ABANDONED DUCT RUN IS CONGESTING EVERYTHING IN IT'S PATH. EXISTING FAN COILS/AIR HANDLERS AUX. OVERFLOW PANS. WHERE ARE DRAINS? WHAT PROVISIONS ARE GOING TO DEAL WITH OVERFLOW SENSORS?
10/30/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED ABOVE CEILING ON PHASE 2. OK FOR CEILING TILES.
10/14/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/INSPECTED ON PHASE 1 ONLY. OK FOR CEILING TILES.