Permit: T03CM04365

Parcel: 128100530

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Permit Number - T03CM04365

Inspection Description - BUILDING ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2003 BUILDING ABOVE CEILING Approved IVRS - Inspection 0000*
11/06/2003 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection 0000* ALL EXCEPT 130 & 131 AREA.
DUCTING REQUIRED TO BE SUPPORTED 4' OC ABOVE GRID. ISOLATED SMALL AREAS WHERE IT IS NECESSARY TO TOUCH GRID ARE OK
11/05/2003 BUILDING ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000* 1) NO DATA CABLES, ELECTRIC CABLES, NOR PLUMBING FOR MECH UNITS SHOULD BE SUPPORTED BY THE CEILING GRID. 2) COMPLETE MISSING T-BAR IN GRID
10/23/2003 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection 0000* PLEASE LIFT DATA CABLES OFF GRID. OK TO PLACE TILE IN ROOMS LISTED ON 10/13/03