Permit: T03CM04358

Parcel: 111062050

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/02/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/01/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) A/C FEEDER AND GFI FOR ROOF TO HAVE CONDUITS FOR PENETRATION AND TO BE SUPPORTED 2) KITCHEN CIRCUITS-NEED 2-20 AMP FOR COUNTER AND MUST HAVE NO-OTHER RECEPTS ON IT REFRIDGERATOR OK NOT DINING ROOM OUTLETS 3) INSTALL FLEX ON WATER HEATER CIRCUIT AND SUPPORT ON STUD 4) PLAN TO BE ON SITE 5) 1-4 FOR UNITS 1 & 2