Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/02/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ELECTRIC SUB PANEL INSIDE HOUSE ADDITION MUST HAVE AN ISOLATED NEUTRAL BAR 2) KITCHEN SINK CANNOT USE CORRIGATED TRAP OR DIRTY ARM. MUST BE SMOOTH INTERIOR SURFACE |
|