Permit: T03CM04339

Parcel: 11009017B

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/28/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/27/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NAIL OFF SIDING OSB UNDER NORTH WINDOW AND AT SHINERS ON EAST WALL-NORTH END 2) NAIL BIRD BOARDS THROUGH ROOF 3) WHERE ROOF SHEATHING ONLY COVERS 1 RAFTER BAY (2 RAFTERS) IT MUST BE BLOCKED UNDERNEATH WITH 2 X AND THEN NAILED THROUGH ROOF 4) CORRECT ROOF SHEATHING INSTALLATION AT NORTHWEST CORNER 5) PROVIDE 1" COMBUSTIBLE CLEARANCE TO WATER HEATER FLUE 6) SHIM OVER AND UNDER HEADERS 7) FIRE BLOCK AT NEW WALL/OLD WALL INTERSECTIONS AT THE LOWEST TOP PLATE OF EITHER 8) NOTE: INTERMEDIATES CANNOT PASS UNTIL MESH IS COMPLETE. DO NOT INSULATE