Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM04327

Parcel: 140374570


Addresses:

6163 E BRAMBLE ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/12/2003 FRAMING Approved IVRS - Inspection 0000*
12/08/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) HOLDOWNS AT GARAGE NOT NAILED, NUT LOOSE AND REPLACE SHEER 2) NO TEST ON DWV'S 3) ELECTRICAL BOX AT HALL BATH UPSTAIRS JUST HANGING 4) NAIL PROTECT ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD AT MASTER BEDROOM AND FIRST FLOOR 5) BLOCK REGISTER AT POWDER ROOM 6) COMPLY WITH TABLE 370.2.1INC
12/05/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) SECURE PLUMBING GOING TO 2ND FLOOR 2) NO WATER TEST AT TOP OUT 3) HOLDOWN NOT NAILED
11/26/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) ROMEX HANGING IN GARAGE 2) FLAT ROMEX NOT ALLOWED TO BE STAPLED ON IT'S SIDE 3) MOVE ROMEX AWAY FROM GUSSETT PLATES 4) FIRE BLOCK MISSING AT WATER HEATER PLATFORM 5) COMPLY WITH DETAIL S4 FOR STAIRS AT CONCRETE 6) HOLDOWNS NOT INSTALLED AND REPLACE SHEAR AT GARAGE 7) STOPPED INSPECTION, TO MANY ITEMS, RECALL WHEN READY