Permit: T03CM04322

Parcel: 10605003A


Addresses:

3901 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM04322

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) 1½" PVC YARDWTR EXTENDED TO RPPBP - EXISTING HOSE BIBBS REMOVED. GALVANIZED CONNECTIONS AT RPPBP OK. OK TO COVER. 2) EXISTING IRRIGATION SYSTEM IS DISCONNECTED. 3) PLBG FINAL OK. 4) OK FOR C OF O PENDING ANY OTHER INSP.
05/25/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/17/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) pvc to maintain 12" of cover at all points. 2) yardwtr to maintain bldg supply all the way to the rppbp as 1½". 3) all reconnected hose bibs to have atmospheric vacuum breakers. 4) contractor to pay re-inspection fee.
05/06/2004 PLUMBING - FINAL Not ready for Inspection
05/04/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*