Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM04322
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ 1) 1½" PVC YARDWTR EXTENDED TO RPPBP - EXISTING HOSE BIBBS REMOVED. GALVANIZED CONNECTIONS AT RPPBP OK. OK TO COVER. 2) EXISTING IRRIGATION SYSTEM IS DISCONNECTED. 3) PLBG FINAL OK. 4) OK FOR C OF O PENDING ANY OTHER INSP. | |
05/25/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/17/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) pvc to maintain 12" of cover at all points. 2) yardwtr to maintain bldg supply all the way to the rppbp as 1½". 3) all reconnected hose bibs to have atmospheric vacuum breakers. 4) contractor to pay re-inspection fee. |
|
05/06/2004 | PLUMBING - FINAL | Not ready for Inspection | ||
05/04/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/03/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) UNCOVER LAST TEN FEET BEFORE BACKFLOW DEVICE RPPBP IS 1" WATER SERVICE-YARD WATER PIPING IS 1 1/2" PVC. SEE 610.2 94 UPC SECOND PARAGRAPH |