Permit: T03CM04322

Parcel: 10605003A


Addresses:

3901 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM04322

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2004 ELECTRIC - FINAL Approved 1) APPROVED PER CONVERSATION WITH RAY MAJUTA OVER THE PHONE ON 6/11/04. ALL ITEMS AS PER M. CAPISTRAN WRITE-UP
05/10/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) PLEASE REFER TO WRITE UP OF 5/3/04 FOR ITEMS REQUIRING ATTENTION
05/03/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) PLANS MUST BE REVISED TO REFLECT DELETED WALLS, ELECTRICAL AND RELOCATED CIRCUITS, REVISE PANEL SCHEDULES AND LOAD CALC'S AS NEEDED 2) REVISE ONE LINE AND SERVICE EQUIPMENT PLAN. ALL PLANS MUST ACCURATELY REFLECT AS BUILT CONFIGURATION