Permit: T03CM04318

Parcel: 124081810


Addresses:

1444 E 9TH ST #01


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM04318

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/11/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CRIMPED ENDS OF VENT CONNECTOR INSTALLED UPSIDE DOWN. DO NOT USE A DOUBLE WALL ELBOW ON TOP OF WATER HEATER INTO A SINGLE WALL TEE. DO NOT USE TAPE ON JOINTS. PROVIDE MINIMUM 3 SCREWS IN EACH JOINT. PROVIDE MINIMUM 6" CLEARANCE AROUND SINGLE WALL VENT CONNECTION FROM COMBUSTIBLES OR USE DOUBLE WALL W/1" CLEARANCE. PROVIDE A TRAP ON CONDENSATE DRAIN LINE. PAINT EXPOSED PVC WITH LATEX PAINT. SECURE DISCONNECTS TO WALL BETTER AT CONDENSORS. DOUBLE WALL VENT MUST EXTEND MINIMUM 5' FROM TOP OF WATER HEATER TO BOTTOM OF DISCHARGE