Permit: T03CM04279

Parcel: 140324530

Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T03CM04279

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2003 ROOF NAILING Approved IVRS - Inspection 0000*
10/24/2003 ROOF NAILING Partial Approval IVRS - Inspection 0000*/ 1) PARTIAL TILL CALCS ARE APPROVED
10/23/2003 ROOF NAILING Denied IVRS - Inspection 0999*/ 1) ROOF NOT NAILED. 2) WIND BRACES REQUIRE TWO NAILS AT THE END. 3) OVERSPAN AT GARAGE EAST WALL. 4) OVERSPANS AT FRONT WINDOW. 5) MISSING ONE VENT. 6) MISSING LRU AT GARAGE EAST WALL FOR DBL TRUSS T34C. 7) PROVIDE LEDGIBLE TRUSS CALCS. 8) SHEER TRANSFERS NOT NAILED PER PLAN.