Permit: T03CM04268

Parcel: 12113626A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) TIGHTEN LOOSE SEAL TITE FITTINGS AT A/C 2) GROUNDING EQUIPMENT CONDUCTOR TO UNIT APPEARS TO BE #12 IT IS TO BE #10 3) UNIT IS OCCUPIED WITHOUT FINAL INSPECTION OR C OF O 4) TIGHTEN LOOSE M/C FITTING AT INSTA-HOT
02/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ OK ABOVE CEILING.