Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/04/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) TIGHTEN LOOSE SEAL TITE FITTINGS AT A/C 2) GROUNDING EQUIPMENT CONDUCTOR TO UNIT APPEARS TO BE #12 IT IS TO BE #10 3) UNIT IS OCCUPIED WITHOUT FINAL INSPECTION OR C OF O 4) TIGHTEN LOOSE M/C FITTING AT INSTA-HOT |
| 02/11/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ OK ABOVE CEILING. |