Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/18/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/04/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FOLLOWING ITEMS FROM 2/10/01 INSPECTION NOT COMPLIED WITH 1, 2, 6 AND 5 2) ATTIC HEAT PUMP DISCONNECT CANNOT BE FED BY TWO SEPERATE CIRCUITS 20 AMP AND 30 AMP. REMOVE ABANDONED CONDCUTORS 3) SECURE #10 WIRE WITHIN 8" OF DISCONNECT 4) PROVIDE ROMEX CLAMP/BUSHING FOR K.O. PENETRATION AT DISCONNECT 5) SUSPEND HEAT PUMP UNIT FROM TOP CHORD OF TRUSSES 6) WEAHTER TIGHT CONNECTION LOOSE 7) ELECTRIC OUTLET NOT ALLOWED UNDER COUNTER WITH OVERHANG GREATER THAN 6" 8) HOT AND NEUTRAL REVERSED LIVING ROOM |
| 02/10/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) BACK WATER VALVE MUST BE ACCESSIBLE EXTEND TO GRADE 2) A/C DISCONNECT HAS LESS THAN 30" X 30" UNOBSTRUCTED WORK AREA 3) OUTLET MISSING BY STAIR 4) ELECTRIC OUTLET GREATER TAHN 6' FROM DINING ROOM 5) STAIR LIGHT FIXTURE CANNOT EXTEND INTO STAIR WELL MORE THAN 4 1/2" BELOW 6'-8" ABOVE STAIRS 6) STAIR HAND RAIL MUST BE CONTINUOUS ALONG WINDERS NARROW SIDE 8) ATTIC A/C HEATER IS MISSING FIELD INSTALLED ELECTRIC DATA PLATE 9) PRESENTLY UNIT CONDUCTORS ARE #10 BEING SERVED BY #12 WIRE FUSED WITH 25 AMP |
| 02/09/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A/C DISCONNECT REQUIRES 30" OBSTRUCTED WORK AREA IN FRONT OF DISCONNECT 2) A/C DISCONNECT HAS IMPROPER COLOR CODE. WHITE HOT 3) A/C HAS OVERSIZED CIRCUIT BREAKER MAXIMUM ALLOWED 40 AMP AND 50 AMP INSTALLED 4) STOPPED INSPECTION TOO MANY ITEMS |
| 02/06/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT COMPLETE PER DAVID SUPER |
| 02/04/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEMS NOT CORRECTED |
| 01/30/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A/C OVER FUSED AND DISCONNECT MISSING BREAKERS AT INSTALL TAG (POST TENSION) WATER SERVICE 2) WRAP BLACK ELECTRICAL TAPE ON WIRE (WHITE) FOR POWER SUPPLY 3) NEED LADDER FOR ATTIC INSPECTION 4) CUT SEWER CLEANOUTS TO GRADE 5) STOPPED INSPECTION |
| 01/28/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCEL |