Permit: T03CM04246

Parcel: 133231430


Addresses:

7877 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/09/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O.
03/02/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCT AS PER 200 IMC. 2) PROVIDE GREASE CUP ON EXHAUST FAN. RECALL FOR FINAL.
02/17/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ OK FOR TEMP C OF O.
02/13/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PAINT EXPOSED BLACK IRON EXHAUST FAN CURB ON ROOF. PROVIDE A GREASE CUP AT FAN OUTLET . 2) PROVIDE A DUCT SMOKE DETECTOR IN AIR HANDLER. CONDENSATE DRAINS ARE OK. RELIEF VENT FROM COOLING TOWER IS OK. NEED TO SEE RELIEF VENT FROM COMPRESSOR RACK. PROVIDE LETTER FROM ENGINEER.