Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM04246
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/04/2004 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ 1) SUPPORT PVC CONDENSATE DRAINS MAXIMUM 4' SPACING 2) PROVIDE A DUCT SMOKE DETECTOR IN AIR HANDLER 3) PLANS CALL FOR 14" X 14" ALUMINIUM DUCT FOR BAKERY OVEN. PROVIDE LETTER FROM ENGINEER IF CHANGING. NEED TO SEE RELIEF VENTS ON COMPRESSORS AND CHILLER. OK FOR CEILING TILES. LEAVE OUT AROUND BAKERY OVEN. WILL CHECK CORRECTIONS ON FINAL 5) PLANS CALL FOR COMBUSTION AIR HIGH AND LOW IN EQUIPMENT ROOM FOR WATER HEATER | |
01/21/2004 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ INSPECTED FIRE WRAP AND ACCESS DOOR. SEAL EXHAUST DUCT ON BAKERY OVEN. NEED TO SEE ABOVE CEILING IN KITCHEN. INSPECTED EXHAUST AND SUPPLY IN RESTROOMS. OK TO SHEET ROCK. WILL CHECK CONDENSATE FROM COOLERS ON FINAL. | |
01/15/2004 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/1) INSPECTED FIRE WRAP ON GREASE DUCT. USE INSULATION PINS OR WRAP AROUND ACCESS DOOR ON WELD ON A STEEL FRAME AROUND OPENING. ACCESS DOOR MUST BE ABLE TO OPEN WITHOUT THE USE OF A TOOL. PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR FIRE WRAP. 2) OK FOR SHEET ROCK IN CASH ROOM. INSULATE NEW SPIRAL DUCTS. 3) NEED TO SEE MAKE UP AIR FOR KITCHEN. 4) BAND MISSING ON FIRE WRAP AT HOOD COLLAR CONFIRMED LETTER FROM ARCHITECT ALLOWING FIRE WRAP. |