Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/09/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SUPPORT CONDUIT AND FLEX FOR NEW CHICKEN DISPLAY. 2) CAN NOT STACK LUGS. 3) FINISH #1 FROM PREVIOUS INSP. |
| 03/02/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CORRECTLY IDENTIFY GROUND CONDUCTOR, AND ONLY ONE PER LUG, CLEAN SURFACE 2) SUPPORT CONDUCTORS AS PER CODE 3) FILL UNUSED OPENINGS 4) A PERMANENT REVISED PANEL SCHEDULES NEEDED AND LABELS ON OUTSIDE COVER 5) FINISH FIRE STOPPING BOTH SWITCH BOARDS 6) USE APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED 7) BOXES MORE THAN 1/4" IN NON COMBUST. TO HAVE EXTENDER RINGS 370.20 8) ICE MACHINE TO HAVE DISCONNECTING MEANS 9) GROUND JUNCTION BOXES 250.148 |
| 02/17/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
1) OK TEMP C OF O FLOOR STOCKING ONLY |
| 02/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ BLANK OR INSTALL DEVICES ON SALES FLOOR AS DICUSSED. OK TO CLOSE REFRIGERATION EQUIPMENT. |