Permit: T03CM04246

Parcel: 133231430


Addresses:

7877 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM04246

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/09/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SUPPORT CONDUIT AND FLEX FOR NEW CHICKEN DISPLAY. 2) CAN NOT STACK LUGS. 3) FINISH #1 FROM PREVIOUS INSP.
03/02/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) CORRECTLY IDENTIFY GROUND CONDUCTOR, AND ONLY ONE PER LUG, CLEAN SURFACE 2) SUPPORT CONDUCTORS AS PER CODE 3) FILL UNUSED OPENINGS 4) A PERMANENT REVISED PANEL SCHEDULES NEEDED AND LABELS ON OUTSIDE COVER 5) FINISH FIRE STOPPING BOTH SWITCH BOARDS 6) USE APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED 7) BOXES MORE THAN 1/4" IN NON COMBUST. TO HAVE EXTENDER RINGS 370.20 8) ICE MACHINE TO HAVE DISCONNECTING MEANS 9) GROUND JUNCTION BOXES 250.148
02/17/2004 ELECTRIC - FINAL Partial Approval 1) OK TEMP C OF O FLOOR STOCKING ONLY
02/13/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/13/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ BLANK OR INSTALL DEVICES ON SALES FLOOR AS DICUSSED. OK TO CLOSE REFRIGERATION EQUIPMENT.