Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 12/12/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) SANITARY "T" FITTINGS NOT ALLOWED FOR USE AS HORIZONTAL DRAIN FITTINGS 2) VENT FITTINGS NOT ALLOWED FOR USE BELOW FLOOD RIM OF FIXTURES 3) TUB NOT PROPERLY VENTED 4) DRAIN CANNOT BE INSTALLED PARALLEL UNDER BLDG FOOTING. PROVIDE NAME AND CONTRACT # OF PLUMBER 5) IMPROPER AIR TEST APPLIED FOLLOW UPC OR PROVIDE WATER TEST |