Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL
06/29/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TO CLEAR UNITS 1 AND 2 TEMP POLE
06/24/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS ENTIRE EXPOSED LENGTH PANEL AND ROOF. 2) CURRENTLY SUPPORT SEALTITE ABOVE CABINET AND IN CABINET. 3) AWITCHES TO BE GROUNDED 380-9. 4) SMOKE DETECTOR TO BE 3' FROM REGISTER. 5) ONLY ONE CONDUCTOR ALLOWED UNDER GROUND SCREW - LIGHTS. 6) WHERE IS WTR AND GAS BONDS? 250-104, 7) SUPPORT DISCONNECTS AND BOXES 8) SUPPORT SEALTITE UP OFF OF ROOF. 9) TIGHTEN TERMINATIONS. - ONLY ONE CONDUCTOR PER TERMINAL AT SERVICE. 10) USE APPROVED BUSHING AT SERVICE FOR CABLES. PLEASE VERIFY FEEDER SIZE. 11) SERVICE COVER RIVITED SHUT.