Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2004 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection :*/ 1) OK TO CLEAR UNITS 1 AND 2 |
| 04/20/2004 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) A BONDING DEVICE IS NEEDED FOR RISER 250-94. 2) STRAP RISER TO STRUCTURE. 3) PVC TO BE SCHEDULE 80. 4) PERMANENT METAL ADDRESS AND UNIT LABELS NEEDED. |