Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2004 | FRAMING | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/15/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) LEDGERS REQUIRED 4-16D NAILS EACH STUD 2) NUTS LOOSE AT GARAGE HOLDOWNS 3) POST BASE AND CAP REQUIRED AT INT. 6 X 6 POST TO BEAMS 4) STAPLE MESH 6" ON CENTER AT BOTTOM OF TOP THRU-OUT 5) NEED WATER TEST ON PLUMBING TOP OUT 6) NO TEST ON GAS LINE |