Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 10/07/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) TRUSS CLISP COVERED WITHOUT INSPECTION APPROVAL 2) NO PRIOR INSPECTION REPORT ON SITE 3) MANY OSB PANELS NOT NAILED TO TRUSSES. RENAIL ALL SHINERS 4) ONE TRUSS NOT NAILED TO OSB 5) TOILET 2" VENT MUST BE 2 1/2" FOR VERTICAL WET VENT FOR LAV DRAIN BOTH TOILETS 6) FRONT TOILET DWV LEAKING |
| 10/03/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) DENIED REFEE DUE 2) STAPLES TO BE FLUSH WITH SHEATHING 3) STOPPED INSPECTION |
| 09/30/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) WRONG PLAN 2) NO PERMIT 3) NO TRUSS DRAWINGS |