Permit: T03CM04151

Parcel: 126050460


Addresses:

4122 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O.
03/30/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*/ COND. PIPING, OLD UNIT INTO NEW LINE, NOT COMPLETE
03/24/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ PROVIDE OUTSIDE AIR INTAKE ON EXISTING A/C UNIT. RELOCATE CONDENSATE ON EXISTING UNIT. INSTALL BIRD SCREEN ON EXISTING VENTS AS PER 2000 IMC.
02/09/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) A/C UNIT IS OVERFUSED. 30 AMP IS MAXIMUM 2) EXTEND WATER HEATER VENT ABOVE EVAP COOLER 3) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON NEW GAS PIPE 4) OK FOR TEMP C OF O