Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/12/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ NO WORK PROGRESS - A RE-FEE HAS BEEN ASSESSED. |
| 04/08/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GROUNDED CONDUCTOR TO BE WHITE PER CODE 200-7. 2) EXPOSED PVC CONDUIT TO BE SCHEDULE 80. |
| 03/24/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ PLANS HAVE BEEN REVISED AND STAMPED. OK WALLS. OK TEMP C OF O - SUBJECT TO OTHER INSP. NEED END CAPS FOR LIGHTING (LV) |
| 02/06/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ SIGNED SHEET FOR TEMP POWER FOR TEST. 1) ADDED CAN LIGHTS TO BE ADDED TO PLANS AND RE-APPROVED FOR INSPECTION. HAVE REVISION STAMPED AT CITY OF TUCSON. |
| 01/26/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ OK TEMP C OF O, KITCHEN SOUTH EAST CORNER OF BLDG. |
| 01/22/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TEMP POWER FOR TEST 2) NO PAPER WORK ON SITE TO ? |
| 01/21/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FOR TEMP POWER: NEED FUSES, REJECTION PINS AND WATER BOND TO NEW WATER LINE |