Permit: T03CM04135

Parcel: 125160780

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/04/2004 FRAMING Approved IVRS - Inspection 0000*
01/28/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) INSTALL AB'S IN MASTER BEDROOM 2) DOUBLE STUDS AT OVER NOTCHED PLUMBING 3) SEAL MOISTURE BARRIER 4) LAP MOISTURE BARRIER PER CODE 5) 1/2" CLEARANCE AT CAN LIGHTS 6) NAIL PLATE CONDUCTORS AT 2 X 4 WALL WITHIN 1 1/4" OF EDGES 7) INSTALL 220V AT WATER HEATER 8) TEST WASTE 9) EXTEND 3" CO AT MB 10) NAIL PLATE WASTE 11) 1/4" PER FOOT AT LAUNDRY SINK TRAP, POWDER ROOM 12) SEAL DUCTS AT TEARS AND CONNECTIONS
01/14/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) LATH NOT DONE
12/11/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*