Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04130
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) WILL NEED TO INSPECT UNDERCOUNTER AND UPLITE INSTALL AND SUPPORTS ON FINAL | |
10/13/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*HCF ( MC ) CABLE CONNECTORS MUST BE HCF W/COPPER INSERT | |
09/27/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) APPROVED CHANGES TO BE ON SITE |
|
09/20/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/15/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) GRPX-I LIGHTING CONTROL CENTER-ROUGH IN . PLEASE KEEP COPY OF ENGINEERS DRAWING ON SITE. ALL WIRING TO PATIENT CARE AREAS MUST BE HCF ( MC CABLE) | |
09/14/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NOTE ALL WIRING FOR RECEPTACLES HAS TO BE PER NEC 99' SECTION 517 2) DO NOT HAVE APPROVED PLAN FOR LAYOUT OF SWITCHING FOR ROOM 121 |
|
09/13/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/01/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) BATHROOMS AND BREAKROOM | |
07/26/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/26/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/01/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/30/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) OK SO WALL FOR PLASTER RINGS FOR 2 LAYER SHEET ROCK 2) OK SOUTH WALL (SHEARWALL) | |
06/29/2004 | ELECTRIC - INTERMEDIATE | Denied | PLASTER RINGS HAVE TO BE DEEP ENOUGH FOR TWO LAYERS OF ROCK. | |
06/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ OK TO INSULATE INSIDE PERIMETER WALL - DO NOT SHEET ROCK TIL ALL MUD RINGS | |
06/25/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ NEED TO FINISH ALL BOXES AND CONNECTIONS TO CONDUITS. |
|
06/03/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONNECT ADDRESS ON OWNERS METER AND PANEL 2498 E. RIVER RD "OW" 2) CT CON CALLS FOR BRACING SEE INSTRUCTIONS INSIDE COVER. 3) NEED TO INSPECT WIRE TERMINATIONS AT CT USED A GROUND BUSHING AND JUMPER TO CAN. |
|
06/01/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ NO ELECTRICAL WORK AT THIS TIME. DENTAL AREA TO BE AS PER 517. |