Permit: T03CM04130

Parcel: 10824012A


Addresses:

2498 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM04130

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) WILL NEED TO INSPECT UNDERCOUNTER AND UPLITE INSTALL AND SUPPORTS ON FINAL
10/13/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*HCF ( MC ) CABLE CONNECTORS MUST BE HCF W/COPPER INSERT
09/27/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) APPROVED CHANGES TO BE ON SITE
09/20/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/15/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) GRPX-I LIGHTING CONTROL CENTER-ROUGH IN . PLEASE KEEP COPY OF ENGINEERS DRAWING ON SITE. ALL WIRING TO PATIENT CARE AREAS MUST BE HCF ( MC CABLE)
09/14/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NOTE ALL WIRING FOR RECEPTACLES HAS TO BE PER NEC 99' SECTION 517 2) DO NOT HAVE APPROVED PLAN FOR LAYOUT OF SWITCHING FOR ROOM 121
09/13/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/01/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/27/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) BATHROOMS AND BREAKROOM
07/26/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/26/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/01/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/30/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK SO WALL FOR PLASTER RINGS FOR 2 LAYER SHEET ROCK 2) OK SOUTH WALL (SHEARWALL)
06/29/2004 ELECTRIC - INTERMEDIATE Denied PLASTER RINGS HAVE TO BE DEEP ENOUGH FOR TWO LAYERS OF ROCK.
06/28/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ OK TO INSULATE INSIDE PERIMETER WALL - DO NOT SHEET ROCK TIL ALL MUD RINGS
06/25/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ NEED TO FINISH ALL BOXES AND CONNECTIONS TO CONDUITS.
06/03/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CONNECT ADDRESS ON OWNERS METER AND PANEL 2498 E. RIVER RD "OW" 2) CT CON CALLS FOR BRACING SEE INSTRUCTIONS INSIDE COVER. 3) NEED TO INSPECT WIRE TERMINATIONS AT CT USED A GROUND BUSHING AND JUMPER TO CAN.
06/01/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ NO ELECTRICAL WORK AT THIS TIME. DENTAL AREA TO BE AS PER 517.